ioPAC 8500 Series (85M) Modules

Module for the ioPAC 8500/8600 Series, 16 DOs, 24 VDC, sink, -40 to 75°C operating temperature

Input/Output Interface
  • Digital Output Channels

    • 16
  • Isolation

    • 3k VDC or 2k Vrms
Digital Outputs
  • Voltage

    • 24 VDC
  • Connector

    • Spring-type Euroblock terminal
  • Current Rating

    • 200 mA per channel
  • I/O Mode

    • DO or PWM
  • I/O Type

    • Sink
  • Over-Current Protection

    • 0.65 A per channel @ 25°C
  • Over-Temperature Shutdown

    • 175°C (typical), 150°C (min.)
  • Pulse Output Frequency

    • 5 kHz
  • Over-Voltage Protection

    • 45 VDC (typical)
Power Parameters
  • Power Consumption

    • 35.4 mA @ 24 VDC
Physical Characteristics
  • Dimensions

    • 25 x 128.2 x 85.5 mm (0.98 x 5.05 x 3.37 in)
  • Weight

    • Under 80 g
  • Wiring

    • I/O cable, 14 to 28 AWG
Environmental Limits
  • Operating Temperature

    • -40 to 75°C (-40 to 167°F)
  • Storage Temperature (package included)

    • -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity

    • 5 to 95% (non-condensing)
  • Altitude

    • 2000 m
      Note: Please contact Moxa if you require products guaranteed to function properly at higher altitudes.
Standards and Certifications
  • EMC

    • EN 55032/24
      EN 61000-6-2/-6-4
  • EMI

    • CISPR 32, FCC Part 15B Class A
  • EMS

    • IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV
      IEC 61000-4-3 RS: 5100 MHz to 6000 MHz: 3 V/m
      IEC 61000-4-4 EFT: Power: 1 kV; Signal: 0.5 kV
      IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV
      IEC 61000-4-6 CS: 10 V
      IEC 61000-4-8 PFMF
  • Railway

    • EN 50121-4
      EN 50155 (complies with a portion of EN 50155 specifications)
  • Safety

    • UL 508
  • Shock

    • IEC 60068-2-27
  • Vibration

    • IEC 60068-2-6
MTBF
  • Time

    • 792,571 hrs
  • Standards

    • Telcordia SR332
Warranty