As of June 15, 2022, this site no longer supports Internet Explorer. Please use another browser for the best experience on our site.
MOXA

Modbus TCP Gateways

Whether single or multiple serial ports, Moxa’s Modbus TCP gateway solutions convert data in networks between Modbus RTU/ASCII, Modbus TCP, DNP3, CANopen, J1939, PROFIBUS, BACnet/IP, IEC 101/104, and IEC 61850, making configuration, troubleshooting, and conversion quick and easy.

MGate 5103
MGate 5103 Series

1-port Modbus/EtherNet/IP-to-PROFINET gateway, 0 to 60°C operating temperature

Ethernet Interface
  • 10/100BaseT(X) Ports (RJ45 connector)

    • 2
      Auto MDI/MDI-X connection
  • Magnetic Isolation Protection

    • 1.5 kV (built-in)
Ethernet Software Features
  • Industrial Protocols

    • PROFINET IO Device, Modbus TCP Client (Master), Modbus TCP Server (Slave), EtherNet/IP Adapter
  • Configuration Options

    • Web Console (HTTP/HTTPS), Device Search Utility (DSU), Telnet Console
  • Management

    • ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, SSH, UDP, NTP Client
  • MIB

    • RFC1213, RFC1317
  • Time Management

    • NTP Client
Security Functions
  • Authentication

    • Local database
  • Encryption

    • HTTPS, AES-128, AES-256, SHA-256
  • Security Protocols

    • SNMPv3
      SNMPv2c Trap
      HTTPS (TLS 1.3)
Serial Interface
  • Console Port

    • RS-232 (TxD, RxD, GND), 8-pin RJ45 (115200, n, 8, 1)
  • No. of Ports

    • 1
  • Connector

    • DB9 male
  • Serial Standards

    • RS-232/422/485
  • Baudrate

    • 50 bps to 921.6 kbps
  • Data Bits

    • 7, 8
  • Parity

    • None, Even, Odd, Space, Mark
  • Stop Bits

    • 1, 2
  • Flow Control

    • RTS Toggle (RS-232 only), RTS/CTS
  • RS-485 Data Direction Control

    • ADDC® (automatic data direction control)
  • Pull High/Low Resistor for RS-485

    • 1 kilo-ohm, 150 kilo-ohms
  • Terminator for RS-485

    • 120 ohms
  • Isolation

    • 2 kV (built-in)
Serial Signals
  • RS-232

    • TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND
  • RS-422

    • Tx+, Tx-, Rx+, Rx-, GND
  • RS-485-2w

    • Data+, Data-, GND
  • RS-485-4w

    • Tx+, Tx-, Rx+, Rx-, GND
Serial Software Features
  • Configuration Options

    • Serial Console
  • Industrial Protocols

    • Modbus RTU/ASCII Master, Modbus RTU/ASCII Slave
Modbus RTU/ASCII
  • Mode

    • Master, Slave
  • Functions Supported

    • 1, 2, 3, 4, 5, 6, 15, 16, 23
  • Max. No. of Commands

    • 128
  • Input Data Size

    • 512 bytes
  • Output Data Size

    • 512 bytes
Modbus TCP
  • Mode

    • Client (Master), Server (Slave)
  • Functions Supported

    • 1, 2, 3, 4, 5, 6, 15, 16, 23
  • Max. No. of Client Connections

    • 16
  • Max. No. of Server Connections

    • 32
  • Max. No. of Commands

    • 128
  • Input Data Size

    • 512 bytes
  • Output Data Size

    • 512 bytes
PROFINET
  • Mode

    • IO Device
  • Max. No. of IO Controller Connections

    • 1 (for read/write)
  • Input Data Size

    • 512 bytes
  • Output Data Size

    • 512 bytes
EtherNet/IP
  • Mode

    • Adapter
  • CIP Objects Supported

    • Identity, Message Router, Assembly, Connection Manager, TCP/IP interface, Ethernet link, Port
  • Max. No. of Scanner Connections

    • 1 (for read-only), 1 (for read/write)
  • Input Data Size

    • 496 bytes
  • Output Data Size

    • 496 bytes
Memory
  • microSD Slot

    • Up to 32 GB (SD 2.0 compatible)
Power Parameters
  • Input Voltage

    • 12 to 48 VDC
  • Input Current

    • 455 mA @ 12 VDC
  • Power Connector

    • Screw-fastened Euroblock terminal
Relays
  • Contact Current Rating

    • Resistive load: 2 A @ 30 VDC
Physical Characteristics
  • Housing

    • Metal
  • IP Rating

    • IP30
  • Dimensions

    • 36 x 105 x 140 mm (1.42 x 4.14 x 5.51 in)
  • Weight

    • 507 g (1.12 lb)
Environmental Limits
  • Operating Temperature

    • 0 to 60°C (32 to 140°F)
  • Storage Temperature (package included)

    • -40 to 85°C (-40 to 185°F)
  • Ambient Relative Humidity

    • 5 to 95% (non-condensing)
Standards and Certifications
  • Safety

    • EN 60950-1, UL 508
  • EMC

    • EN 55032/24
  • EMI

    • CISPR 32, FCC Part 15B Class B
  • EMS

    • IEC 61000-4-2 ESD: Contact: 8 kV; Air: 15 kV
      IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m
      IEC 61000-4-4 EFT: Power: 4 kV; Signal: 2 kV
      IEC 61000-4-5 Surge: Power: 2 kV; Signal: 2 kV
      IEC 61000-4-6 CS: 150 kHz to 80 MHz: 10 V/m; Signal: 10 V/m
      IEC 61000-4-8 PFMF
  • Hazardous Locations

    • ATEX, Class I Division 2, IECEx
  • Freefall

    • IEC 60068-2-32
  • Shock

    • IEC 60068-2-27
  • Vibration

    • IEC 60068-2-6, IEC 60068-2-64
MTBF
  • Time

    • 859,422 hrs
  • Standards

    • Telcordia SR332
Warranty
Added To Bag
You have some items waiting in your bag; click here to finish your quote!
Feedback